Gateway network requirements
For IT teams approving a Control Seat gateway on a plant or office network. The short version: the gateway makes one outbound encrypted connection, to your Control Seat workspace on port 443, and needs nothing from outside.
At a glance
| Outbound | HTTPS and secure WebSocket to <your workspace>.controlseat.app, TCP 443 |
| Inbound | None. No port forwarding, VPN, public IP or static public address |
| Allow by | Host name. The cloud's IP addresses change, so an IP allow list will break |
| Proxy | HTTP proxy (CONNECT) or SOCKS5, with an optional user name and password |
| TLS inspection | Supported once the gateway trusts your inspection certificate |
| DNS and time | Your DHCP-provided servers, or ones you set on the gateway |
| Addressing | DHCP or a fixed IPv4 address, on Ethernet or Wi-Fi |
| Device approval | Each gateway's MAC addresses are on its setup sheet, its label and its page in Control Seat |
What the gateway connects to
| Destination | Port | What for |
|---|---|---|
<your workspace>.controlseat.app | TCP 443 | Everything Control Seat does: your data, commands, software updates and link checks. One long-lived connection that reconnects by itself |
| Your DNS servers | UDP and TCP 53 | Looking up the workspace address |
| Your time servers | UDP 123 | Keeping the clock right. A secure connection needs the clock within a few minutes of the real time |
| Your DHCP server | UDP 67 and 68 | An address, unless you give the gateway a fixed one |
| Plant devices you connect | Their own ports, for example Modbus TCP 502, EtherNet/IP 44818, OPC UA 4840 | Only the devices you set up, on your network |
The gateway does not contact any other Control Seat host or cloud storage service: software updates arrive over the same connection on port 443. If public time servers are blocked, give the gateway your own (see below), or hand them out with DHCP option 42.
Nothing comes in
Control Seat needs no inbound connection. The gateway's Control Seat services listen only on the gateway itself, unless you set up a connector that serves your network, such as a Modbus TCP server for another system to read.
How the connection is secured
- TLS 1.2 or newer, with TLS 1.3 preferred. The gateway checks the server's certificate and name against its trusted certificates.
- There is no certificate pinning, so a firewall that inspects TLS works once the gateway trusts that firewall's certificate authority. Add it as the gateway's site certificate.
- The gateway proves who it is with a credential created on the gateway when it is enrolled. Only a fingerprint of it ever leaves the gateway.
- Control Seat can send the gateway only Control Seat's own commands: data and device settings, PLC programs, and network settings. There is no remote shell.
- A network change made from Control Seat is tried first and kept only if the gateway can still reach Control Seat. Otherwise the gateway goes back to its earlier settings by itself within a few minutes.
- Software updates are signed, and the gateway checks the signatures before it installs one.
Settings you can give the gateway
Set these during setup (in the Control Seat app over Bluetooth, or on the gateway's own setup page), or later from the gateway's page in Control Seat.
- Ethernet: automatic (DHCP) or a fixed IPv4 address with its gateway and DNS servers, on gateways whose Ethernet port Control Seat manages. An industrial PC whose Ethernet your team configured keeps that configuration. For an equipment network without internet, give a fixed address without a gateway: the gateway then never sends anything else that way. A fixed address is checked first, so one another device already uses is refused, not taken over.
- Wi-Fi: WPA2 or WPA3 with a password; WPA2 or WPA3 Enterprise (802.1X) with a user name and password, using PEAP, or TTLS with PAP or MSCHAPv2; and open networks. For Enterprise Wi-Fi you can give the CA certificate and the server's domain, so the gateway joins only your network's real server (TTLS with PAP requires one of them). Hidden networks work. The same fixed-address choices apply as for Ethernet.
- Time servers: up to three, by name or address.
- Web proxy:
http://host:portorsocks5://host:port, with an optional user name and password. The gateway uses it only for its connection to Control Seat; connections to your plant devices never go through it. Proxies that require Windows (NTLM or Kerberos) sign-in are not supported: allow the gateway through by its MAC or IP address instead. - Site certificate: the certificate authority of a firewall that inspects TLS, in PEM format.
- Cellular: on gateways with a modem, the APN is chosen automatically from the SIM, or you can set it.
Not supported: certificate-based Wi-Fi sign-in (EAP-TLS), WEP, captive portal networks, and IPv6-only networks without NAT64. The gateway needs IPv4, or NAT64 and DNS64, to reach Control Seat.
More than one connection
When a gateway has more than one way to connect, it prefers wired Ethernet, then Wi-Fi, then cellular, and moves to the next one by itself when a link stops working. A proxy you set is used for the Control Seat connection on whichever link carries it.
Approving the device
Each gateway shows its MAC addresses:
- on its printed setup sheet and on the label inside its cabinet;
- in the Control Seat app, under Other network settings, in the section For your IT team;
- on the gateway's page in Control Seat, beside each link.
The gateway always uses the address built into its hardware, never a random one, so the printed address is the one your network sees.
Setting it up on site
A new gateway can be set up without your network: over Bluetooth from the Control Seat app, or through its own setup Wi-Fi.
- The setup Wi-Fi uses WPA2 with a password unique to the unit. It reaches only the gateway's setup page, never your network.
- Bluetooth setup is encrypted and needs the gateway's setup code.
- Both are on for the first hour after the gateway powers on, and whenever it has not reached Control Seat for 10 minutes. A workspace admin can also open them from Control Seat.
- Wrong setup codes are limited: after five, the gateway makes the person wait between tries, up to 10 minutes.
If the connection drops
The gateway keeps collecting data and sends it when the connection comes back. By default it keeps up to 24 hours; your workspace can set up to 7 days.
Data use
The connection carries a small heartbeat every 10 seconds plus your data. How much depends mostly on how many sensors and tags you connect and how often they report. For a cellular plan, ask Control Seat for an estimate for your site.
Checklist
- Allow outbound TCP 443 to
<your workspace>.controlseat.appby host name, directly or through your proxy. - Make sure the gateway can reach DNS and a time server, or give it your own.
- If your firewall inspects TLS, export its CA certificate for the gateway.
- Approve the gateway's MAC addresses if your network requires it.
- Decide between DHCP and a fixed address, and Wi-Fi details if it will use Wi-Fi.